GAMI
شركة الخليج لصناعة المكيفات ذ.م.م
Gulf Air Conditioning Manufacturing Industries LLC.
AT ESP 50 pa
HIGH STATIC STANDARD WATER ΔΤ FAN COILS
MOTOR AT HIGH SPEED
AIR FLOW
TOTAL CAPACITY
SENSIBLE CAPACITY
SHF
WATER FLOW
WATER PRESSURE DROP
MOTOR
DIMENSIONS(mm)
MODELS
m3/h
CFM
KW
BTU/H
Kpa
watt
RPM
LENGTH
WIDTH
HEIGHT
GFC-09-300-HS-3R
510
300
2.7
9212
2.18
7438
0.81
0.46
19
80
1060
750
635
GFC-09-300-HS-4R
3.22
10987
2.46
8394
0.76
0.55
33
1090
GFC-09-300-HS-6R
3.82
13034
2.8
9554
0.73
0.66
23
1180
650
GFC-12-400-HS-3R
680
400
3.62
12351
2.88
9827
0.80
0.62
35
120
1105
850
GFC-12-400-HS-4R
3.96
13512
3.09
10543
0.78
0.68
1145
GFC-12-400-HS-6R
5.11
17435
3.73
12727
0.88
40
150
1260
GFC-15-500-HS-3R
500
4.33
14774
3.54
12078
0.82
0.74
21
1150
GFC-15-500-HS-4R
5.05
17231
3.98
13580
0.79
0.87
16
1205
GFC-15-500-HS-6R
6.1
20813
4.52
15422
1.05
18
180
1290
GFC-18-600-HS-3R
1020
600
4.98
16992
4.07
13887
0.85
25
1100
GFC-18-600-HS-4R
5.86
19994
4.64
15832
1.01
1175
GFC-18-600-HS-6R
7.58
25863
5.53
18868
1.3
46
GFC-24-800-HS-3R
1360
800
6.83
23304
5.38
18357
1.17
54
250
1130
GFC-24-800-HS-4R
8.04
27432
6.28
21427
1.38
44
1225
GFC-24-800-HS-6R
1200
706
8.79
29991
6.51
22212
1.51
27
1240
GFC-30-1000-HS-3R
1700
1000
8.67
29582
6.97
23782
1.49
29
1450
GFC-30-1000-HS-4R
10.7
36508
8.21
28013
0.77
1.84
51
1185
GFC-30-1000-HS-6R
12.2
41626
9.04
30844
2.09
350
GFC-36-1200-HS-3R
2040
10.6
36167
8.36
28524
1.82
43
1650
GFC-36-1200-HS-4R
12.6
42991
9.64
32892
2.17
47
1095
GFC-36-1200-HS-6R
14.9
50839
11.1
37873
2.55
GFC-42-1400-HS-3R
2380
1400
11.7
39920
9.51
32448
2.01
24
450
1850
660
GFC-42-1400-HS-4R
13.5
46062
10.8
36850
2.32
1190
GFC-42-1400-HS-6R
17.6
60051
12.9
44015
3.02
34
1250
700
GFC-48-1600-HS-3R
2720
1600
13.7
46744
2.34
50
GFC-48-1600-HS-4R
16.1
54933
2.76
41
550
1115
GFC-48-1600-HS-6R
19.4
66193
14.5
49474
0.75
3.33
1195
GFC-60-2000-HS-3R
3400
2000
15.9
54251
13.3
45380
0.84
2.73
26
1230
1800
GFC-60-2000-HS-4R
18.8
64146
15.1
51521
GFC-60-2000-HS-6R
3000
1765
21.7
74040
54592
0.73733
THE ABOVE DATA ARE BASED ON THE FOLLOWING CONDITIONS
AIR FLOW QUANTITY REFERENCED TO STANDARD CONDITIONS (27 C DB/19 C WB)
WATER FLOW RATE BASED ON STANDARD WATER ΔΤ (7C IN 12 C OUT)
AIR INLET TO THE COIL 27 C DB 19 C WB
EXTERNAL STATIC PRESSURE 50 pa