GAMI

شركة الخليج لصناعة المكيفات ذ.م.م

Gulf Air Conditioning Manufacturing Industries LLC.

[Chillers] [models] [Technical Information Page 1] [Technical Information page 2] [Data R22 page1] [Data R22 page 2] [Data R407C page1] [Data R407 C page2]

GENERAL DATA FOR R407C

Model

Step Type

CCU75ATG

CCU100ATG

CCU120ATG

CCU150ATG

CCU180ATG

CCU200ATG

CCU220ATG

CCU240ATG

Continuous Control Type

CCU75ATGZ

CCU100ATGZ

CCU120ATGZ

CCU150ATGZ

CCU180ATGZ

CCU200ATGZ

CCU220ATGZ

CCU240ATGZ

Nominal CoolingCapacity *1

50Hz

kW

191

280

346

382

519

573

626

692

kcal/h

164,260

240,800

297,560

328,520

446,340

492,780

538,360

595,120

Btu/h

651,000

955,000

1,180,000

1,303,000

1,771,000

1,955,000

2,136,000

2,361,000

Nominal CoolingCapacity *2

50Hz

kW

158

243

301

315

451

473

544

601

kcal/h

135,600

209,300

258,900

271,200

387,900

406,900

467,900

517,200

Btu/h

538,000

831,000

1,026,000

1,076,000

1,539,000

1,614,000

1,857,000

2,052,000

Capacity Control

 

 

Step Type

%

100, 75, 50, 0

100, 75, 50, 25, 0

100, 66, 33, 17, 0

100, 75, 50, 38, 25, 13, 0

Continuous Type

%

100 ~ 25, 0

100 ~ 25, (12.5) *3, 0

100 ~ 25, (8.3) *3, 0

100 ~ 25, (12.5) *3, 0

Dimension

 

 

Height

mm

2,400

2,400

2,400

2,400

2,400

2,400

2,400

2,400

Width

mm

1,800

1,800

1,800

1,800

1,800

1,800

1,800

1,800

Depth

mm

2,130

3,930

3,930

3,930

5,730

5,730

7,960 (min.)

7,960 (min.)

Refrigerant

R407C (Factory Charged)

Refrigerant flow Control

Thermostatic Expansion Valve with MOP

Number of Circuits

1

2

2

2

3

3

4

4

Compressor Type

Semi-Hermetic Screw Type

Compressor model

Step Control

6005SC-HP

5005SC-HP

6005SC-HP

6005SC-HP

6005SC-HP

6005SC-HP

5005SC-HP

6005SC-HP

Quantity

1

2

2

2

3

3

2

4

 

 

 

 

 

 

 

6005SC-HP

 

 

 

 

 

 

 

2

 

Continuous Control

6005SC-ZP

5005SC-ZP

6005SC-ZP

6005SC-ZP

6005SC-ZP

6005SC-ZP

5005SC-ZP

6005SC-ZP

Quantity

1

2

2

2

3

3

2

4

 

 

 

 

 

 

 

6005SC-ZP

 

 

 

 

 

 

 

2

 

Heat Exchangers

 

 

 

 

 

 

 

 

 

Condenser

Louvre Fin-Inner grouved copper tube 3/8” staggered heat exchanger

Condenser Fan

Direct Drive Propeller Fan

Motor

kW

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

Quantity

4

8

8

8

12

12

2 x 8

2 x 8

Water Cooler(Evaporator)

Plate Type

Type of Control System

Micro-Processor Control

Safety Devices

Quick Response Relay for Compressor (R, T Phase), Internal Thermostat for Compressor,

Reverse Phase Protection device for Compressor, Thermal Overcurrent Relay for Fan Motor,

High Pressure Switch, Low Pressure Control, Suction Gas Temperature Control, Freeze Protection Thermistor Control,

Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief valve

Connections

Victaulic Type

Water Cooler Inlet/Outlet

3B

2 x 3B

3 x 3B

4 x 3B

Net Weight

kg

1,650

2,870

3,020

3,080

4,430

4,500

2,870+3,020

2 x 3,020

Approximate Shipping Dimensions *4

 

 

Height

mm

2,730

2,740

2,740

2,740

2,760

2,760

2 x 2,740

2 x 2,740

Width

mm

2,140

2,190

2,190

2,190

2,190

2,190

2 x 2,190

2 x 2,190

Depth

mm

2,300

4,150

4,150

4,150

5,950

5,950

2 x 4,150

2 x 4,150

Shipping Weight *4

kg

2,070

3,530

3,680

3,740

5,230

5,300

3,530+3,680

2 x 3,680

NOTES:1. The nominal cooling capacities are based on the following conditions. (*1)

 Chilled Water Inlet/Outlet Temperature: 12 / 7oC Condenser Air Inlet Temperature: 35oC (DB)
The effective cooling capacities are based on the following conditions. (*2)
 Chilled Water Inlet/Outlet Temperature: 12 / 7oC Condenser Air Inlet Temperature: 46oC (DB)

2. Power Source : Main (AC 3f) 380 / 415V 50Hz
 : Control (AC 1
f) 220 / 240V 50Hz

3. The units greater than 220ATX including 220ATX consist of two modules and are separately shipped. (*4)

4. Water Flow
 1) CPC240, 300, 320, 360, 370, 400ATG(Z)
 It is necessary to control the same water quantity to each cooler.
 The common chilled water piping (Field-Supplied) between each water cooler shall be directly connected at site.
 (The water coolers in the same unit shall be connected to the same common piping.)
 2) CPC24, 270, 310, 330, 380AGT(Z)
 The chilled water flow rate is different between No.1 and No.2 units.
 It is necessary to control the water quantity of each unit with adjusting valves as dimensional drawing.

 

[Home] [About] [Products] [Chillers] [Fan Coils] [AHU Modular] [GDA AHU] [Downloads] [HVAC Lab] [Factory] [Contact Us]